Door Selection, Hygiene Zones and Cleaning Regimes in Food Production
Published:
Publisher: Alkur Kapı Sistemleri A.Ş.
By: Ercan Erdoğan
Door selection in a food facility starts with hygiene zones, users and cleaning conditions rather than a product name. This guide produces a requirements and verification record matching the facility hygiene plan to the dealer’s proposed door/automation scope. Facility/project parties provide conditions and the dealer product/installation scope; Alkur does not perform site surveys or on-site services.
From hygiene zone to product decision
- Name the two zones. Record goods-in, preparation, processing, packing and despatch passages separately. The facility team states which temperature, pressure or cross-contamination target concerns the door.
- Separate people and vehicles. Record pedestrians/forklifts, load size, two-way use, peak periods and hold-open time. Fast closing alone does not prove pressure or hygiene performance.
- Choose the opening command. Assess buttons, hand sensors, radar or vehicle detection against the actual passage. Touch-free opening can remove a shared contact surface; cleaning compatibility and safety need separate verification.
- Define safety scope. Match closing path, photocell/safety edge and stopping function to the model document. An activation sensor is not automatically a safety sensor.
- Specify cleaning. The facility states chemical, concentration, method, washing/pressure and frequency. Verify curtain, coating, seals, motor and sensors separately; one IP rating or material name does not establish washability of the complete system.
- Compare product and document scope. Identify door, motor/controller, sensor and loading-equipment model/revision. Do not invent disinfectant resistance, hygiene certification or sensing range absent from the technical sheet.
- Verify operation at the facility. The dealer’s authorised team records movement and safety checks; the facility hygiene team evaluates cleaning and zone targets in its own verification plan. Resolve open confirmations before closing the record.
Activation and safety serve different functions
| Equipment | Role in the decision | Scope to verify |
|---|---|---|
| Hand sensor / button | Opening command for authorised passage | Detection/contact arrangement, controller input, cleaning compatibility |
| Radar | Opening request within its documented detection zone | Coverage, unwanted activation and actual model function |
| Loop detector | Vehicle-presence command/detection | Vehicle/loop match; not pedestrian detection or access permission |
| Photocell | Safety response through the documented beam/input | Position, coverage and closing behaviour |
| Safety edge | Documented contact/edge protection | Door-controller pairing and functional test |
| STOP | Installed system stopping function | Input, operating mode and model test procedure |
Multiple activation sources are connected according to the controller’s input/contact diagram. “All can be wired in parallel” is not a general rule; activation and safety inputs are not interchangeable.
Confirm against material and model data
Roll-up and folding HPVC specifications describe 900 g/m² Panama-weave PVC curtains, respectively 80 × 80 mm aluminium and 200 × 200 mm galvanised steel uprights. Both list up to 1.5 m/s with an inverter; this is not a fixed transit time, pressure-retention or disinfectant-resistance declaration. Glazing, bottom seals and installed safety configuration are stated separately in the quotation.
The hand sensor sheet documents 24 V, NO/COM and sensitivity adjustment, not 5–15 cm range, stainless/plastic housing or disinfectant resistance. The technician matches it to the chosen door/controller documents; detection testing is not proof of cleaning suitability.
The R2-equipped automatic door system in the LUVI manual lists 150 kg single-leaf and 120 + 120 kg double-leaf limits. They do not apply to every pedestrian mechanism or telescopic system. Verify closing/safety behaviour and leaf configuration in the actual model documents.
Documents and hygiene acceptance
The NORMDOCK shelter requirements for 3 mm/900 g/m² PVC, DIN 53352/53356/75200, antistatic and stain-resistant properties are not independent HACCP/GMP certification. Hygiene assessment concerns the facility plan and installed configuration. Record seal contact or visible gaps; light leakage is not a particle-permeability test. Complete-door performance is verified within the relevant declaration/test scope.
Output: hygiene-passage verification record
Record zone pair, pedestrian/vehicle profile, temperature/pressure target, chosen activation and separate safety function, cleaning conditions, model/document identity, check results and open confirmations. Assign each confirmation to the dealer, project or facility party. Touch-free operation, speed or a material name then remains a documented input rather than a standalone “hygienically suitable” conclusion; its basis and follow-up remain visible.
Sources and evidence
Original sources for this publication and the specific information each link supports.
- NORMDOCK dock shelter technical specification, REV03 (opens in a new tab) PDF language: TR / EN
- Publisher:
- Alkur Kapı Sistemleri
- URL
- alkur.com.tr
- Last verified:
Claim supported: Page 2 lists PVC fabric values, DIN requirements, construction and dimensions. These manufacturer requirements do not constitute an independent test certificate, HACCP/GMP qualification or full-isolation guarantee.
- r-tec hand sensor connection sheet (opens in a new tab) PDF language: EN
- Publisher:
- Alkur Kapı Sistemleri
- URL
- alkur.com.tr
- Last verified:
Claim supported: PDF page 1 documents 24 V wiring, NO/COM contacts and sensitivity adjustment. It does not specify detection range, housing material or disinfectant resistance.
- ALKUR roll-up HPVC door specification (opens in a new tab) PDF language: TR / EN
- Publisher:
- Alkur Kapı Sistemleri
- URL
- alkur.com.tr
- Last verified:
Claim supported: The specification describes curtain and structural dimensions and speeds for its own door type. These values do not establish an automatic RAPID, FU or I-380 pairing.
- ALKUR folding HPVC door specification (opens in a new tab) PDF language: TR / EN
- Publisher:
- Alkur Kapı Sistemleri
- URL
- alkur.com.tr
- Last verified:
Claim supported: The specification describes curtain and structural dimensions and speeds for its own door type. These values do not establish an automatic RAPID, FU or I-380 pairing.
- r-tec LUVI automatic door manual (opens in a new tab) PDF language: TR
- Publisher:
- r-tec
- URL
- alkur.com.tr
- Last verified:
Claim supported: PDF p.5: the documented R2-equipped system has 150 kg single-leaf/120 + 120 kg double-leaf limits and a closing photocell response. Not generalised to other mechanisms or telescopic systems.